LSZH vs PVC Jacket: Indoor Fire-Rating Choice

LSZH vs PVC Jacket: Indoor Fire-Rating Choice

PVC burns with dense smoke; LSZH costs a little more and keeps the escape route visible. How OFNR, OFNP and LSZH ratings map to buildings, and what to write on the order.

The optical performance of a jacket is identical; its behavior in a fire is not. Jacket choice is the one cable decision a building inspector reads first, and it is decided before the first meter is pulled. For an indoor tight-buffered cable or any cord order, the jacket line on the order sheet is a code decision.

The rating ladder

JacketTypical ratingBest fitFire behavior
PVCGeneral indoor (CM/OFNR variants)Offices and equipment roomsDense smoke, halogen acid gas
LSZHIEC 60332-1/-3Risers, public corridors, tunnels, enclosed routesLow smoke, no halogen acid gas
Plenum (OFNP)North American plenumAir-handling spacesStrictest common rating
Outdoor PEOutdoor onlyOutside plantNot permitted indoors

What codes usually ask

  • Risers require a riser-rated jacket (OFNR or equivalent fire-rated LSZH per local code).
  • Air-handling plenums require plenum-rated OFNP in North American practice.
  • Public and enclosed routes increasingly specify LSZH, especially in EU-influenced markets.
  • Always verify the local clause. Ratings differ between markets; the inspector's edition governs, not the catalog.

Ordering notes the jacket changes

  • LSZH jackets run slightly larger in OD; tray fill and bend-radius planning stay routine.
  • Optical parameters do not move: ≤0.3 dB typical / ≤0.5 dB max IL and UPC ≥50 dB / APC ≥60 dB RL for OS2 cords regardless of jacket.
  • State the rating on the order line itself, so the packing list and the inspector see the same words.

Key specifications at a glance

ParameterTypical value
Jacket optionsPVC, LSZH, OFNR, OFNP; PE outdoor only
Cable typesTight-buffered indoor, distribution, patch cords
Insertion loss (connectorized ends)≤0.3 dB typical / ≤0.5 dB max (1310/1550 nm)
MOQ1,000 pcs (adapters) / 100 pcs (cords); cable per drum
Lead time7–15 working days after deposit
Payment30% T/T deposit, balance before shipment
Warranty12 months from shipment date

Rating names follow common market usage; local code clauses and the shipped datasheet govern each project.

Buyer FAQ

Which is stricter, LSZH or OFNP?

OFNP is the strictest North American rating. LSZH is the European-style answer for smoke and halogens; the two are selected by code environment, not by a single scale.

Can LSZH replace plenum cable?

Only where the local authority accepts it. In North American plenums the answer is usually no; elsewhere LSZH often satisfies riser and public-route clauses.

Does the jacket affect optical performance?

No. IL and RL are set by the fiber and the ferrules; the jacket decision is mechanical and fire-safety only.