LSZH vs PVC Jacket: Indoor Fire-Rating Choice
PVC burns with dense smoke; LSZH costs a little more and keeps the escape route visible. How OFNR, OFNP and LSZH ratings map to buildings, and what to write on the order.
The optical performance of a jacket is identical; its behavior in a fire is not. Jacket choice is the one cable decision a building inspector reads first, and it is decided before the first meter is pulled. For an indoor tight-buffered cable or any cord order, the jacket line on the order sheet is a code decision.
The rating ladder
| Jacket | Typical rating | Best fit | Fire behavior |
|---|---|---|---|
| PVC | General indoor (CM/OFNR variants) | Offices and equipment rooms | Dense smoke, halogen acid gas |
| LSZH | IEC 60332-1/-3 | Risers, public corridors, tunnels, enclosed routes | Low smoke, no halogen acid gas |
| Plenum (OFNP) | North American plenum | Air-handling spaces | Strictest common rating |
| Outdoor PE | Outdoor only | Outside plant | Not permitted indoors |
What codes usually ask
- Risers require a riser-rated jacket (OFNR or equivalent fire-rated LSZH per local code).
- Air-handling plenums require plenum-rated OFNP in North American practice.
- Public and enclosed routes increasingly specify LSZH, especially in EU-influenced markets.
- Always verify the local clause. Ratings differ between markets; the inspector's edition governs, not the catalog.
Ordering notes the jacket changes
- LSZH jackets run slightly larger in OD; tray fill and bend-radius planning stay routine.
- Optical parameters do not move: ≤0.3 dB typical / ≤0.5 dB max IL and UPC ≥50 dB / APC ≥60 dB RL for OS2 cords regardless of jacket.
- State the rating on the order line itself, so the packing list and the inspector see the same words.
Key specifications at a glance
| Parameter | Typical value |
|---|---|
| Jacket options | PVC, LSZH, OFNR, OFNP; PE outdoor only |
| Cable types | Tight-buffered indoor, distribution, patch cords |
| Insertion loss (connectorized ends) | ≤0.3 dB typical / ≤0.5 dB max (1310/1550 nm) |
| MOQ | 1,000 pcs (adapters) / 100 pcs (cords); cable per drum |
| Lead time | 7–15 working days after deposit |
| Payment | 30% T/T deposit, balance before shipment |
| Warranty | 12 months from shipment date |
Rating names follow common market usage; local code clauses and the shipped datasheet govern each project.
Buyer FAQ
Which is stricter, LSZH or OFNP?
OFNP is the strictest North American rating. LSZH is the European-style answer for smoke and halogens; the two are selected by code environment, not by a single scale.
Can LSZH replace plenum cable?
Only where the local authority accepts it. In North American plenums the answer is usually no; elsewhere LSZH often satisfies riser and public-route clauses.
Does the jacket affect optical performance?
No. IL and RL are set by the fiber and the ferrules; the jacket decision is mechanical and fire-safety only.
Entscheidungshilfe
Mantelentscheidung
Durch welchen Raum verläuft das Kabel?
Lösungsangebot anfordern
Beschreiben Sie Ihr Einsatzszenario, die benötigten Steckertypen, Faserzahlen und Zielmengen. Je spezifischer Ihre Angaben, desto schneller können unsere Ingenieure die passenden Produkte und die Lieferzeit bestätigen.